NEK606 Instrumentation Cables S11 RU(i) 250V:
Applications
These unarmoured cables are flame retardant, low smoke and halogen free, used for instrumentation, communication, control and alarm systems.
Standards
IEC 60092-376 IEC 60092-351
IEC 60092-359 IEC 60332-1
IEC 60332-3-22 IEC 60754-1,2
IEC 61034-1,2 NEK 606:2004
Construction
- Conductors : Circular tinned annealed stranded copper wire to IEC 60228 class 2.
- Insulation : Halogen free EPR compound.
- Twinning : Colour coded cores twisted together.
- Individual Shielding : Each pairs/triples are screened by copper backed polyester tape in contact with a stranded tinned copper drain wire and wrapped with polyester tape. Pairs/triples are numbered with numbered tape or by numbers printed directly on the insulated conductors.
- Outer Sheath : Halogen free thermosetting compound, SHF2, coloured grey (blue for intrinsically safe).
Technical data:
Nominal Cross Section Area | mm² | 0.75 | 1 | 1.5 | 2.5 |
Nominal Conductor Diameter | mm | 1.1 | 1.3 | 1.6 | 2 |
Maximum Resistant@20℃ | Ω/km | 26.3 | 19.3 | 12.9 | 8.02 |
Mutual Capacitance | nF/km | 90 | 100 | 110 | 120 |
Nominal Inductance@1KHz | MH/km | 0.686 | 0.649 | 0.637 | 0.598 |
Maximum L/R@1KHz | μH/Ω | 20 | 25 | 35 | 50 |
Operating Voltage | V | 250 | 250 | 250 | 250 |
Mechanical and Thermal Properties
- Bending Radius : 8×OD (during installation); 6×OD (fixed installed).