JIS C 3410 Power & Lighting Cable 0.6/1.0KV:
CABLE DESIGNATION
0.6/1kV SPYC, SPYCY, FA-SPYC, FA-SPYCY
0.6/1kV SPYCB, SPYCBY, FA-SPYCB, FA-SPYCBY
APPLICATION STANDARD
- Design guide : JIS C 3410(1999)
- Flame retardant : IEC 60332-1 & IEC 60332-3 Category A (FA-Type)
- Cold bend/impact : CSA 22.2 No. 03 (-35 ℃) (Cold Type)
- Max. conductor temperature : 85℃
Cable Type: 0.6/1kV (FA-)SPYC, 0.6/1kV (FA-)SPYCY, 0.6/1kV (FA-)SPYCB, 0.6/1kV (FA-)SPYCBY
No. of Cores: 1 Core
Nominal Area: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 300.
Technical Data:
Classification | Code | Construction Detail |
Conductor | S |
Stranded tinned annealed copper
wires as per JIS C 3410. 2. Insulation |
Insulation | P | EPR as per JIS C 3410. |
Sheath | Y | PVC as per JIS C 3410. |
Armor |
C (CB) |
Braid of copper alloy wires (-CB
type) or galvanized steel wires (-C type).C6 Coverage density is minimum 90%. |
Paint |
The white paint shall be painted
uniformly on the steel wire braid CB Type or Protective covering Type, paint is dispensable |
|
Protective Covering | Y |
PVC as per JIS C 3410. Outer sheath color : Black |