JIS C 3410 0.6/1kV (FA-)SPYCBS, 0.6/1kV (FA-)SPYCBYS Power and Lighting Cable:
CABLE DESIGNATION
0.6/1kV SPYCBS, FA- SPYCBS
0.6/1kV SPYCBYS, FA- SPYCBYS
0.6/1kV DPYS, TPYS, FA-DPYS, FA-TPYS
0.6/1kV DPYCS, TPYCS, FA-DPYCS, FA-TPYCS
0.6/1kV DPYCYS, TPYCYS, FA-DPYCYS, FA-TPYCYS
APPLICATION STANDARD
- Design guide : JIS C 3410(1999)
- Flame retardant : IEC 60332-1 & IEC 60332-3 Category A (FA-Type)
- Cold bend/impact : CSA 22.2 No. 03 (-35℃ ) (Cold Type)
- Max. conductor temperature : 85℃
TECHNICAL DATA
1. CABLE TYPE:0.6/1kV (FA-)SPYCBS, 0.6/1kV (FA-)SPYCBYS
No. of Cores : 1 core
Nominal Area(mm2):1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120.
2. CABLE TYPE:0.6/1kV (FA-)DPYS, 0.6/1kV (FA-) DPYCS, 0.6/1kV (FA-)DPYCYS
No. of Cores : 2 core
Nominal Area(mm2):1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120.
3. CABLE TYPE:0.6/1kV (FA-)TPYS, 0.6/1kV (FA-)TPYCS, 0.6/1kV (FA-)TPYCYS
No. of Cores : 3 core
Nominal Area(mm2):1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120.
Classification | Code | Construction Detail | ||
Conductor |
S(D,T) | Stranded tinned annealed copper wires as per JIS C 3410. | ||
Insulation | P | EPR as per JIS C 3410. | ||
Cabling |
Insulated conductors
shall be cabled. Flame retardant & non-hygroscopic fillers may be used. Suitable tape(s) may be applied on the cabled core. |
|||
Common shield | S | Tinned copper wire braid | ||
Sheath | Y | PVC as per JIS C 3410. | ||
Armor |
C (CB) |
Braid of copper alloy
wires (-CB type) or galvanized steel wires (-C type). Coverage density is minimum 90%. |
||
Paint |
The white paint shall
be painted uniformly on the steel wire braid Protective covering Type, paint is dispensable. |
|||
Protective Covering | Y |
PVC as per JIS C
3410. Outer sheath color : Black |
||
Core identification | No. of cores | Insulation Color | ||
1C | Black | |||
2C | Black, White | |||
3C | Black, White, Red |